TwinSAFE enables networks with up to 1,024 TwinSAFE devices. The TwinSAFE PLC can establish 128 connections to other TwinSAFE devices. Multiple TwinSAFE PLCs are cascadable within a network. The EtherCAT Terminal features certified safety function blocks, which are configured according to the application to be realised. Safety functions such as emergency stop, safety door monitoring, two-hand control, etc. can thus easily be selected and linked. All blocks can be freely connected among each other and are complemented by operators such as AND, OR, etc. The required functions are configured via the TwinCAT System Manager and loaded into the EL6900 TwinSAFE PLC via the fieldbus. The EL6900 is suitable for applications up to SIL 3 according to IEC 61508 and DIN EN ISO 13849 PLe.
| Technical data | EL6900 |
|---|---|
| Technology | TwinSAFE PLC |
| Safety standard | IEC 61508 SIL 3 and DIN EN ISO 13849-1:2008 PLe |
| Protocol | TwinSAFE/FSoE |
| Status display | 4 LEDs |
| Connections to other TwinSAFE devices | max. 128 |
| Function blocks | max. 255 |
| Cycle time | 500 µs…~25 ms |
| Current consumption E-bus | approx. 188 mA |
| Fault response time | ≤ watchdog time (parameterisable) |
| Bit width in the process image | 6…1,498 bytes |
| Supply voltage | 24 V DC (-15 %/+20 %) |
| Special features | backup restore |
| Weight | approx. 50 g |
| Operating/storage temperature | 0…+55 °C/-25…+70 °C |
| Permiss. degree of contamin. | 2 |
| Climate class EN60721-3-3 | 3K3 |
| Electrical interference | EN 61000-6-2/EN 61000-6-4 |
| Vibration/shock resistance | EN 60068-2-6/EN 60068-2-27/29 |
| Installation position | horizontal |
| Protection class | IP 20 |
| Approvals | CE, UL, Ex, TÜV Süd |
![]() |
![]() |