The EP2816 EtherCAT Box with digital outputs connects the binary control signals from the controller on to the actuators at the process level. The sixteen outputs handle load currents of up to 0.5 A each, although the total current is limited to 4 A. This makes these modules particularly suitable for applications in which not all of the outputs are active at the same time, or in which not all of the actuators draw 0.5 A current. An output short-circuit is recognised and passed on to the controller.
The signal state is indicated in groups by means of light emitting diodes. The signal connection is realised by a 25-pin D-sub socket (EP2816-0008) or two 9-pin D-sub sockets (EP2816-0010). All outputs are short-circuit-proof, protected against inverse connection and can be diagnosed.
| Technical data | EP2816-0008 | EP2816-0010 |
|---|---|---|
| Number of outputs | 16 | |
| Output connections | D-sub socket, 25-pin | 2 x D-sub socket, 9-pin |
| Protocol | EtherCAT | |
| Load type | ohmic, inductive, lamp load | |
| Nominal output voltage | 24 V DC (-15 %/+20 %) | |
| Max. output current | 0.5 A each channel, individually short-circuit-proof, total current max. 4 A | |
| Short circuit current | max. 1.5 A | |
| Distributed clocks | yes | |
| Auxiliary power current | typ. 20 mA + load | |
| Current consumption from US (without sensor current) | 120 mA | |
| Power supply connection | feed: 1 x M8 male socket, 4-pin; downstream connection: 1 x M8 female socket, 4-pin | |
| Bit width in the process image | 16 outputs, 16 inputs (diagnostics) | |
| Electrical isolation | 500 V | |
| Special features | ideal for valve terminals | |
| Weight | approx. 165 g | |
| Operating/storage temperature | -25…+60 °C/-40…+85 °C | |
| Vibration/shock resistance | conforms to EN 60068-2-6/EN 60068-2-27/29 | |
| EMC immunity/emission | conforms to EN 61000-6-2/EN 61000-6-4 | |
| Protect. class/installation pos. | IP 65/66/67 (conforms to EN 60529)/variable | |
| Approvals | CE, UL | |
![]() |
![]() |
![]() |